SOP Fire Pumps

SOP Fire Pumps

Start/Stop of  Hyd/Sprinkler Jockey pump in"Auto mode" mode
Ensure that power is available for Jockey pump panel
Switch ON the Jockey pump MCCB
Keep the selector swich in AUTO mode
Ensure that both inlet and outlet valves of the pump are in open condition
If the pressure in the FHS line drops below 7.5 kg/cm2 the pump will automatically START and when pressure in the line reached above 8.5 kg/cm2 the pump will STOP
When the motor is running ensure no water leakages in the valves
Starting the Hyd/Sprinkler Jockey pump in Manual mode
Ensure that power is available for Jockey pump panel
Switch ON the Jockey pump MCCB
Keep the selector swich in Manual  mode
Ensure that both inlet and outlet valves of the pump are in open condition
If the pressure in the FHS line is below 7.5 kg/cm2.Switched ON the pump by pressing START push button on the Jockey pump panel (if the pressure exceeds 8.5 kg/cm2 pls switched off the pump by using stopping procedure
Ensure ON indication lamp glows on the panel visually
Ensure that pump is opearating and no water leakages in the water line


Stopping the Hyd/Sprinkler Jockey pump in Manual mode

Ensure that selector swich on the panel is in Manual  mode
Press the STOP push button in the jockey pump panel
Ensure OFF indication lamp glows visually on the panel
Ensure that pump is stopped

3 comments:

  1. Interesting post! I truly admire your knowledge when it come for this fields. Thanks for sharing!

    Fire Extinguisher Sales & Service in Las Vegas

    ReplyDelete
  2. This comment has been removed by the author.

    ReplyDelete
  3. Hello,
    This one is a worth reading article you have shared.
    Thanks for sharing!!

    Fire pumps

    ReplyDelete